EXERIMENTAL CALCULATIONS :

Diameter of Orifice, mm (d1) =34

Diameter of pipe, mm (d2) =68

Coefficient of discharge Cd= 0.6
Density of manometer fluid (water),w (kg/m3)  =1000

Density of air, (kg/m3)  =1.126

g = 9.81 m/s2

Flow rate = 70 ltr/hr

 

S. No. T1 T2 T3 T4 T5 T6 R1(cm) R2(cm) QW (LPH)
1  19  17.5  38.6  36  44.5  30.5  5.6  9.5  3.9
2  19.5  18.1  35.4  34.4  43.7  28.3  3  12.1  9.1
3  20 18.7 35.1  34  44.1  28  0.2  14.1  13.9

 

CALCULATIONS :

 =34.54 m

a1 =Cross Section area of Orifice, m2= 907.46 *10-6  m   

a2 = Cross Section area of pipe, m2 =3629.84*10-6 m

  = 0.01463 m3/s

 nbsp;= 0.0165 kg/s

 =0.01944 kg/s

=1.178

From Enthalpy table, the enthalpy of entering air at a wet bulb temp i.e.17.5 0C is h1= 15.274 Btu/lb of air

                    =15.274 + 1.178(44.5-30.5)

                    =31.766 Btu/lb of air

 

         T,0F                             hwi                        hai              
T=T2 =63.5 hw =   -------- ha  = h1  =15.274   --------
T=T2 +0.1(T1-T2)=63.77 hw =32.12 ha  = h1+0.1(L/G)(T5-T6) =18.25
 13.87
T=T2 +0.4(T1-T2)=64.56 hw =33.12  ha  = h1+0.4(L/G)(T5-T6) =27.19  5.93
T=T2 -0.4(T1-T2)=65.12 hw =33.62  ha  = h2-0.4(L/G)(T5-T6)= 19.84  13.78
T=T2 -0.1(T1-T2)=65.93 hw =34.11  ha  = h2-0.1(L/G)(T5-T6) = 28.78  5.33
T=T1  =66.2 hw =34.32  ha  = h2 = 31.76  2.56

 

Cooling range = T5-T6  = 140C

Temperature approach =T2-T6 = -130C

                    =

                     = 0.501

Now tower characteristics

             =1.7535

 On doing the similar calculations for different values of (L/G),we get the complete calculation table.From there we draw a graph between tower characteristics and (L/G).

 

 

 

 